Experimental Testing
25 years of experimental validation in the world's most prestigious laboratories

Screenshot 2026-03-08 at 14.12.36.png

Applus

Flag of Spain.svg.webp

2026

Screenshot 2026-03-06 at 16.14.41.png

LADICIM

Flag of Spain.svg.webp

2020

Screenshot 2026-03-04 at 11.12.01.png

UNAM

Screenshot 2026-03-04 at 11.12.58.png

2018

images.jpeg

UNINA

Flag_of_Italy.svg.png

2016

Screenshot 2026-03-04 at 11.03_edited.jpg

PUCP

images (2).png

2015

Screenshot 2026-03-04 at 11.03_edited.jpg

PUCP

images (2).png

2014

Screenshot 2026-03-04 at 11.03_edited.jpg

PUCP

images (2).png

2013

Screenshot 2026-03-04 at 10.56.08.png

ISMES

Flag_of_Italy.svg.png

2001

images.png

LMEC

Flag_of_Portugal_(official).svg.png

2000

DISIPADORES SLB: SUPERANDO LOS ESTÁNDARES GLOBALES

DISIPADORES SLB: SUPERANDO LOS ESTÁNDARES GLOBALES
DISIPADORES SLB: SUPERANDO LOS ESTÁNDARES GLOBALES

DISIPADORES SLB: SUPERANDO LOS ESTÁNDARES GLOBALES

02:06
ensayo disipador sismico SLB en Universidad Federico III en Napoles

ensayo disipador sismico SLB en Universidad Federico III en Napoles

00:15
Ensayo histeretico disipador SL30_2

Ensayo histeretico disipador SL30_2

01:25

Latest Test

Experimental Validation (2026) Bellaterra Laboratory

Applus+ Laboratories / Autonomous University of Barcelona (UAB), Spain

 

• Mechanical characterization of SLB dampers (specimens tested from the Shear Link Bozzo / BDSL series, covering heights of 30, 45 and 60 cm and thicknesses of 29 and 34 mm). 

• Full stability at displacements of ±100 mm (reaching maximum actuator strokes of up to ±100 mm and isolated cycles of up to 150 mm, with load capacities of up to 995.49 kN). 

• Verification of hysteretic capacity and energy dissipation (validated through pseudo-static cyclic fatigue testing to failure and continuous fatigue testing of more than 4,900 cycles without failure).

 

Summary of key parameters:

  • Laboratory: Applus+ Laboratories (LGAI Technological Center S.A., Bellaterra, Barcelona).

  • Report date: 25 March 2026 (testing carried out between 16 January and 19 March 2026).

  • Load and stroke range tested: Actuator of up to ±1,000 kN (100 tonnes / +85 t) and ±100 mm of stroke.

  • Maximum load recorded: 995.49 kN in tension and −1,016.65 kN in compression (model BDSL30_34_3).